Thread Failure Under Tensile Loading

← All engineering notes

1. Introduction

Threaded tension members are among the most common structural components in mechanical and civil engineering practice. Tie rods, turnbuckles, tensioners, hangers, and bracing elements are routinely constructed from threaded rods, and their design is conventionally reduced to the verification of a bar in tension. The engineer selects a diameter, checks the tensile stress against the yield strength or the tensile resistance, and considers the member verified. This procedure is applied with equal confidence to the shank and to the threaded section, the latter being treated simply as a reduced cross-section for which the tensile stress area As is substituted for the gross area.

The verification so obtained is correct within its own scope, but the scope is narrower than is commonly assumed, and it is narrower in a direction that is specifically mechanical rather than structural. The tensile check addresses one failure mode only: rupture of the threaded section under a uniaxial tensile force. It does not address thread stripping, the distribution of load over the engaged threads, the combined action of tension and torsion at the thread root during tightening, the friction that generates that torsion, the wear of the thread caused by relative displacement between the rod and the nut, or the strength hierarchy between the threaded rod and the component into which it is engaged. These are distinct failure modes and distinct degradation mechanisms, governed by distinct resistances and distinct tribological conditions, and none of them is represented by the tensile resistance formula. The fact that a threaded member satisfies the tensile verification is therefore not, by itself, evidence that the threaded assembly will perform its function.

The mechanical character of the thread becomes apparent as soon as the tensioning operation is examined rather than the tensioned state. A threaded member is tensioned by rotating a nut or a turnbuckle body relative to the rod. The rotation is resisted by friction on the thread flanks and on the bearing surfaces, and the torque required to produce a given tension is therefore a function of the friction condition, not only of the geometry. In an unlubricated connection, the coefficient of friction on the thread flanks may be of the order of 0.15 to 0.25, and the torque required to develop a given tension is correspondingly high. The rod does not experience a pure tensile stress during the operation: it experiences tension and torsion simultaneously, the torsion being transmitted through the thread from the nut to the shank. The tensile verification, which considers a uniaxial stress state, does not represent this condition.

The same relative rotation that generates the torsion also generates relative displacement between the rod thread and the nut thread. The displacement is small in magnitude, of the order of the elastic deformation of the engaged threads, but it is repeated at every tensioning and re-tensioning operation, and it occurs under high contact pressure. The thread flanks are therefore subjected to a fretting-like contact condition, in which the combination of normal pressure and cyclic micro-slip produces wear of the contacting surfaces. The wear modifies the thread profile, redistributes the contact pressure over the engaged threads, and, in the long term, reduces the effective engagement length. A thread that was verified on the basis of its nominal geometry may therefore possess a lower capacity after several tensioning cycles than the nominal calculation indicates. This degradation mechanism is invisible to the tensile verification and is not ordinarily considered in the design of tension members.

The distinction acquires practical significance in a load case that is frequently absent from the design brief: the re-tensioning of an element that has lost part of its initial tension. A tension member that has been installed and tensioned to its design value may subsequently require re-tensioning as a result of creep, relaxation, settlement of supports, seasonal thermal movement, or loss of preload. The re-tensioning operation is performed through the thread, by rotating a nut or a turnbuckle body, and the force applied during the operation must overcome the existing tension, the desired increment, the friction in the thread and in the turnbuckle, and, where the thread has worn, the increased friction associated with the modified contact condition. This force is not, in general, force-controlled. It is applied by torque, and the torque–tension relationship is subject to a scatter that is difficult to bound without a calibrated wrench and a controlled friction condition.

The consequence is that the force transmitted through the thread during re-tensioning may significantly exceed the force for which the member was verified, and that the thread itself may be in a worse condition than the nominal calculation assumes. If the thread capacity is lower than the shank capacity — a situation that arises whenever the strength hierarchy between the rod and the engaging component is not explicitly enforced — the thread may fail during the re-tensioning operation, even though the shank verification predicted an ample margin. The failure is then attributed to the member, although the member itself was correctly proportioned for the load case it was designed for; the deficiency lies in the verification that was not performed, and in the mechanical phenomena — friction, torsion, and wear — that the verification did not represent.

The present article examines this situation through a representative example: an M24 threaded rod of property class 8.8, engaged in a coupler of length sufficient to develop the thread, and loaded in service to 150 kN. The civil engineer's verification of the shank is carried out and is shown to be satisfied with a utilisation of approximately 74 %. The mechanical engineer's verification of the thread is then carried out, and the thread is shown to be the governing component at the re-tensioning force, with a stripping resistance lower than the tensile resistance of the rod. The re-tensioning load case is examined in detail, including the absence of force control, the torque–tension scatter, and the effect of friction on the torsion transmitted to the rod. The combined action of tension and torsion at the thread root is shown to produce yielding at a force well below the tensile resistance, and the wear of the thread under repeated tensioning is discussed as a degradation mechanism that reduces the capacity of the assembly over its service life.

The objective of the article is not to criticise the civil engineer's verification, which is correct within its scope. It is to demonstrate that the scope is narrower than the design brief ordinarily assumes, that the thread has its own failure modes, its own degradation mechanisms, and its own resistance, and that the re-tensioning load case must be included explicitly in the design brief if the threaded assembly is to be verified as a system rather than as a bar. The argument is developed quantitatively, so that the reader may verify the logic and apply it to other configurations.

2. Problem Statement & Geometry

2.1 Configuration of the tension member

The member considered in the present analysis is a threaded tension rod of nominal diameter d=24 mm and property class 8.8, engaged at each end in a coupler of length sufficient to develop the thread. The rod is loaded in service by a tensile force NE d=150 kN, and it is subsequently re-tensioned by rotation of the coupler relative to the rod, in the manner described in Section 5.

The thread is a metric coarse thread of pitch P=3 mm. The basic dimensions of the thread, referred to the ISO 68-1 profile, are as follows: the nominal diameter is d=24 mm, the pitch diameter is

d2=d−0.6495P=24−0.6495⋅3=22.051 mm,

the minor diameter of the external thread is

d3=d−1.2269P=24−1.2269⋅3=20.319 mm,

and the thread flank angle is 60∘, corresponding to a half-angle α=30∘. The tensile stress area, defined in ISO 898-1 as the area corresponding to the mean of the pitch and minor diameters, is

As=π4(d2+d32)2=π4(22.051+20.3192)2=353mm2,

and the minor-area of the thread root, defined by the minor diameter d3, is

A3=π4d32=π4⋅20.3192=324.3mm2.

The distinction between As and A3 is relevant to the subsequent analysis. The tensile resistance of the rod is conventionally evaluated with As, which represents the mean threaded section and which is the section used in the tensile verification of the bolt. The stress state at the thread root, by contrast, is evaluated with A3, which represents the smallest section and which governs the local yielding that precedes failure by stripping. The two areas differ by approximately 8 %, and this difference is part of the reason why the shank verification and the thread verification do not lead to the same conclusion.

2.2 Material properties

The rod is of property class 8.8. The nominal yield strength is fyb=640 MPa, and the nominal ultimate strength is fub=800 MPa. The stress–strain behaviour of the material is ductile, with a well-defined yield plateau and a substantial elongation at fracture, and the ductility is normally invoked to justify the plastic redistribution assumptions discussed in Section 6.

The coupler is of steel grade S355, with a lower-bound tensile strength Rm=470 MPa. The shear strength of the coupler material is estimated by the von Mises criterion as

τ=Rm3≈0.577Rm≈0.6Rm=282 MPa.

The value τ=282 MPa is adopted as the shear strength of the engaged thread, and it is used in Section 4 to estimate the stripping resistance of the coupler thread. The choice of Rm rather than Rp0.2 is deliberate: the stripping resistance is governed by shear failure of the thread, which occurs at the ultimate condition of the material rather than at its yield, and the use of Rm is therefore appropriate for the resistance function.

The thread engagement length at each end is Le=18 mm, corresponding to Le/d=0.75. This value lies below the engagement length of 1.0d that is ordinarily recommended for the full development of the bolt strength, and it is deliberately adopted here to represent a coupler that has been proportioned for geometric convenience rather than for the strength hierarchy of the threaded assembly.

2.3 Loading

Two loading conditions are distinguished.

The service condition is defined by the tensile force NE d=150 kN, applied along the axis of the rod and transmitted through the coupler to the adjacent structure. This is the load case for which the member is ordinarily designed, and it is the load case represented by the civil engineer's tensile verification.

The re-tensioning condition is defined by the force that must be applied through the thread in order to restore the tension of the stretched element. This force is not a single deterministic value. It comprises the existing tension in the member, the increment required to restore the design tension, and the additional force required to overcome friction in the thread and in the bearing surfaces of the coupler. In the present example the re-tensioning force is taken to lie in the range

Nret=185to200 kN,

the upper bound corresponding to an unlubricated thread with a high friction coefficient and a larger than nominal increment, and the lower bound to a lubricated thread with a smaller increment. The range is intended to represent the scatter that is observed in practice when the tightening operation is not force-controlled. The midpoint of the range, Nret≈190 kN, is adopted as the representative value in the calculations of Sections 4 and 5.

2.4 Tribological parameters

The mechanical behaviour of the thread during tensioning depends on the friction condition at the thread flanks and at the bearing surfaces. Two parameters are accordingly introduced as variables of the example.

The coefficient of friction on the thread flanks is denoted μ. For steel-on-steel threaded connections, the coefficient lies in the range μ≈0.10 for a well-lubricated thread to μ≈0.25 for a dry, unlubricated thread with a lightly oxidised or contaminated surface. An intermediate value of μ≈0.15 is representative of a thread in normal workshop condition without specific lubrication. The coefficient enters the torque–tension relationship through the friction angle

ρ=arctan⁡(μcos⁡α),

where α=30∘ is the half-angle of the thread flank, and cos(α)=0.866. The factor 1/cos(α) accounts for the inclination of the thread flank relative to the axis of the screw, which increases the effective normal force on the flank for a given axial load.

The coefficient of friction at the bearing surface of the coupler is denoted μc. It is taken to be of the same order as μ, although the bearing condition differs from the thread condition because the contact area is larger and the surface finish is different. In the torque calculation of Section 4.3, the contribution of the bearing friction is evaluated separately from the contribution of the thread friction, and the total tightening torque is the sum of the two.

The lubrication state of the thread is treated as a binary variable: lubricated (μ≈0.10) or unlubricated (μ≈0.25). The intermediate condition is represented by the nominal value μ≈0.15. The distinction is significant because the torque required to develop a given tension is approximately proportional to the friction coefficient, and the scatter between the lubricated and unlubricated conditions is therefore of the order of a factor of two in the applied torque. This scatter is the principal reason why the re-tensioning force is not force-controlled in practice, and it is the basis of the discussion in Section 5.

2.5 The two verifications to be compared

The present analysis compares two verifications that are ordinarily performed by different engineers, in different contexts, and for different purposes.

The civil engineer's verification treats the rod as a bar in tension and checks the tensile resistance of the threaded section against the service load. It is performed in accordance with the design rules for steel connections, it uses the tensile stress area As, and it is expressed as a utilisation ratio NE d/Ft, R d. It is the verification that appears in the design calculation for the tension member, and it is the verification that is ordinarily understood as "the verification of the rod".

The mechanical engineer's verification treats the threaded assembly as a system of components and checks the resistance of the thread against the force that is actually transmitted through it. It considers the stripping of the thread, the distribution of load over the engaged threads, the combined action of tension and torsion at the thread root, and the strength hierarchy between the rod and the coupler. It is performed in accordance with the design rules for threaded fasteners, it uses the shear area of the engaged thread and the stress state at the thread root, and it is expressed as a comparison between the applied force and the thread capacity. It is the verification that is ordinarily performed for bolts in mechanical assemblies, and it is the verification that is ordinarily omitted for tension members in civil structures.

The problem addressed in the following sections is the demonstration that these two verifications do not lead to the same conclusion for the configuration defined above, and that the omission of the second verification is the origin of the failure mode described in Section 1.

3. The Civil Engineer's Verification: Shank Rupture Under Tensile Load

3.1 The tensile verification of the threaded section

The verification of a threaded tension member in civil engineering practice is performed in accordance with the rules for tension members, applied to the threaded section. The resistance of the threaded section is evaluated by the same expression that is used for bolts in tension, in which the tensile stress area As is substituted for the gross area and a calibration factor k2 is introduced to account for the difference between the nominal tensile strength and the actual failure load of a threaded section.

The design tensile resistance of the threaded section is

Ft,Rd=k2fubAsγM2,

in which k2=0.9 for ordinary bolts and threaded rods, fub=800 MPa is the nominal ultimate strength of the class 8.8 material, As=353 mm2 is the tensile stress area, and γM2=1.25 is the partial factor for resistance of bolts and threaded members against rupture.

Substituting the numerical values,

Ft,Rd=0.9⋅800⋅3531.25=2541601.25=203328 N=203.3 kN.

The yield resistance of the threaded section, evaluated with the same area and with the partial factor γM0=1.0 for the yield check, is

Nt,y,Rd=AsfybγM0=353⋅6401.0=225920 N=225.9 kN.

The governing resistance is therefore the rupture resistance Ft, R d=203.3 kN, and the yield resistance Nt, y, R d=225.9 kN is not reached before rupture. This ordering is a consequence of the partial factors: the effective design strength in rupture is k2fub/γM2=0.9⋅800/1.25=576 MPa, whereas the effective design strength in yield is fyb/γM0=640 MPa. The rupture criterion therefore governs, and the verification of the member reduces to the check

NEd≤Ft,Rd.

3.2 The utilisation at service load

For the service load NE d=150 kN, the utilisation ratio against the governing rupture resistance is

NEdFt,Rd=150203.3=0.738,

that is, approximately 74 %. Against the yield resistance, the utilisation is

NEdNt,y,Rd=150225.9=0.664,

that is, approximately 66 %. The member is therefore verified with a margin of approximately 26 % against rupture and approximately 34 % against yield. The corresponding stress in the tensile stress area at service load is

σs=NEdAs=150000353=425 MPa,

which is well below the yield strength of 640 MPa and far below the ultimate strength of 800 MPa. In the terms in which the civil engineer ordinarily reports the result, the member "resists" with a comfortable margin.

3.3 What the verification covers

The verification expressed by Ft, R d is the verification of rupture of the threaded section under a uniaxial tensile force. It is based on a stress state in which the tensile stress is uniform over the area As, and it is calibrated against tests on bolts and threaded rods loaded in pure tension until fracture. The calibration factor k2=0.9 accounts for the difference between the nominal strength fubAs and the actual failure load, which is slightly lower as a result of the triaxial stress state at the thread root, the bending of the thread flanks, and the geometric imperfection of the thread profile. The verification is therefore an empirical, test-calibrated check of the rupture load of a threaded section, and it represents the failure mode that is observed when a threaded rod is pulled in pure tension until it breaks.

The verification is legitimate within this scope. It is the check that the design rules require, it is calibrated against the relevant tests, and it produces a resistance that corresponds to a well-defined physical failure mode. The fact that it does not represent other failure modes is not a deficiency of the check itself; it is a consequence of the fact that the check addresses one failure mode and not several.

3.4 What the verification does not cover

The tensile verification does not cover the following failure modes and degradation mechanisms, each of which is governed by a distinct resistance and a distinct physical process.

Thread stripping. The verification assumes that the thread is capable of transmitting the full tensile force of the rod to the engaging component. It does not verify that the engaged length is sufficient for this transmission, and it does not evaluate the shear resistance of the thread. The stripping resistance of the thread is a separate quantity, governed by the shear strength of the engaged material and by the engaged length, and it is not represented by Ft, R d. As shown in Section 4, the stripping resistance of the coupler considered here is lower than Ft, R d, so that the thread is the governing component although the tensile verification predicts an ample margin for the rod.

Load distribution over the engaged threads. The verification assumes that the tensile force is transmitted uniformly through the threaded section. In reality the load is distributed non-uniformly over the engaged threads, with the first engaged thread carrying a substantially larger share than the subsequent ones. The local stress at the first thread is therefore higher than the nominal stress NE d/As, and the local condition at the thread is more severe than the tensile verification indicates. This non-uniformity is not represented by the verification, which is based on a uniform stress over the tensile stress area.

Combined tension and torsion. The verification assumes a uniaxial tensile stress state. During the tightening and re-tensioning operations, however, the rod is subjected simultaneously to tension and to torsion transmitted through the thread. The resulting stress state at the thread root is biaxial, and the equivalent stress is higher than the uniaxial tensile stress for the same axial force. The tensile verification does not represent this condition, and the utilisation ratio that it produces at service load does not reflect the stress state that prevails during the re-tensioning operation.

The strength hierarchy between rod and coupler. The verification addresses the rod only. It does not verify that the coupler is stronger than the rod, and it does not enforce the principle that the failure of the assembly should occur in the rod rather than in the thread. This principle, which is fundamental to the design of threaded fasteners and which is implemented in ISO 898-2 by the requirement that nuts be over-tapped and of a suitable property class, is not enforced by the tensile verification of the rod. The verification therefore does not detect the situation in which the coupler is the weaker component.

Wear and degradation of the thread. The verification is performed on the nominal thread geometry at the beginning of the service life. It does not account for the wear of the thread that may occur as a result of repeated tensioning operations, nor for the reduction of the effective engagement length that such wear produces. The capacity that the verification predicts is therefore the capacity of the thread in its initial condition, not the capacity of the thread after a number of service cycles.

None of these omissions is, in itself, a criticism of the tensile verification. Each of them corresponds to a failure mode or degradation mechanism that is outside the scope of the verification, and each of them is addressed by a distinct method in the discipline that is concerned with it. The criticism, if any, is directed at the assumption that the tensile verification is sufficient, and at the omission from the design brief of the checks that would address the remaining failure modes.

3.5 The legitimacy and the limits of the verification

The tensile verification of the rod is correct, and it is sufficient for the load case and the failure mode it addresses. A tension member that satisfies NE d≤Ft, R d will not fail by rupture of its threaded section under the service load. The verification is therefore not wrong, and the engineer who performs it is not making an error.

The limit of the verification is one of scope rather than of arithmetic. The verification answers the question "will the rod rupture under the service load?", and it answers it correctly. It does not answer the questions "will the thread strip during re-tensioning?", "will the combined tension and torsion at the thread root produce yielding?", "is the coupler stronger than the rod?", or "will the thread remain capable of transmitting the load after repeated tensioning?". These questions require distinct verifications, and the fact that they are not performed is not a consequence of a mathematical error in the tensile check but of a difference in scope between the check that is performed and the checks that the integrity of the assembly requires.

The remainder of the article is devoted to the verifications that address these questions, and to the demonstration that their omission is the origin of the failure mode described in Section 1. The civil engineer's verification establishes that the rod is adequate; the mechanical engineer's verification establishes whether the thread is. The two are not alternatives, and neither substitutes for the other.

4. The Mechanical Engineer's Verification: Thread Capacity

4.1 Thread stripping

The thread transmits the tensile force of the rod to the coupler through the engaged threads. The resistance of the engagement to stripping is governed by the shear strength of the coupler material and by the shear area of the engaged thread. For an internal thread of nominal diameter d engaged over a length Le, the shear area is estimated as

Ashear≈0.5πdLe,

in which the factor 0.5 accounts for the fact that the shear occurs over approximately half the thread height, the remainder being occupied by the clearance between the external and internal thread flanks. For the present geometry, with d=24 mm and Le=18 mm,

Ashear=0.5⋅π⋅24⋅18=678.6mm2.

The stripping resistance is obtained by multiplying the shear area by the shear strength of the coupler material:

Fstrip=Ashearτ=678.6⋅282=191365 N=191.4 kN.

The stripping resistance is therefore lower than the tensile resistance of the rod, Ft, R d=203.3 kN, by approximately 6 %. The thread is the weaker component of the assembly, and it is the component that governs the resistance of the connection.

The engagement length at which the stripping resistance would equal the tensile resistance of the rod is obtained by setting Fstrip=Ft, R d and solving for Le:

0.5πdLe,reqτ=Ft,Rd⟹Le,req=Ft,Rd0.5πdτ=2033280.5⋅π⋅24⋅282=19.13 mm.

The required engagement length corresponds to Le, req/d=19.13/24=0.80. The actual engagement length of 18 mm, corresponding to Le/d=0.75, lies just below this value. The thread is therefore marginally inadequate, and the inadequacy is of the order that is easily overlooked in a verification that does not evaluate the thread explicitly.

The exact stripping resistance depends on the tolerance class of the thread, on the thread form, and on the distribution of load over the engaged threads, and a rigorous verification should be performed in accordance with VDI 2230 or with the provisions of ISO 898-2 for the property class of the nut or coupler. The estimate given above is sufficient to establish the order of magnitude of the resistance and to identify the engagement length at which the thread becomes the governing component. It is not a substitute for the detailed calculation, but it is sufficient to demonstrate that the thread capacity is comparable to the rod capacity for the engagement length considered here.

4.2 Load distribution over the engaged threads

The estimate of the stripping resistance given in Section 4.1 assumes that the load is uniformly distributed over the engaged threads. This assumption is not correct. The load distribution over the threads of a bolted connection is non-uniform, and it has been analysed since the classical work of Sopwith. The first engaged thread, i.e. the thread nearest to the loaded face of the coupler, carries a substantially larger share of the load than the subsequent threads, because the stiffness of the engaged thread and of the surrounding material decreases with distance from the loaded face. For a connection with an engagement length of the order of 0.75d to 1.0d, the first thread carries approximately 30 % to 35 % of the total load, the second thread carries approximately 20 % to 25 %, and the remaining threads carry progressively smaller shares.

For the present connection, with six engaged threads over Le=18 mm, the first thread carries approximately 33 % of the total load. At the re-tensioning force of Nret=190 kN, the first thread therefore carries

F1≈0.33⋅190=62.7 kN.

The shear area associated with a single thread is, on average,

Ashear,1=Ashearnthreads=678.66=113.1mm2,

and the local shear stress at the first thread is

τ1=F1Ashear,1=62700113.1=554 MPa.

This local stress exceeds the shear strength of the coupler material, τ=282 MPa, by a factor of approximately 1.96. The first thread is therefore loaded beyond its shear capacity at the re-tensioning force, and local yielding of the thread occurs.

The physical significance of this result requires careful interpretation. The elastic distribution calculated by Sopwith cannot be maintained once the first thread yields; the local yielding causes a redistribution of load towards the subsequent threads, and the distribution at failure is more uniform than the elastic prediction. The nominal stripping resistance of 191.4 kN represents the load at which all threads reach their shear capacity simultaneously, which is the limit of full plastic redistribution. The actual stripping resistance lies between the load at which the first thread yields and the nominal value, depending on the ductility of the thread material and on the capacity of the thread to redistribute load without fracture.

The essential point for the present argument is not the exact value of the stripping resistance, but the localisation of the load at the first thread. This localisation is the physical origin of stripping initiation, and it is entirely invisible to the shank verification. The shank verification is based on a uniform stress NE d/As over the tensile stress area, and it does not represent the concentration of load at the first engaged thread. A thread that is nominally adequate on the basis of a uniform distribution may therefore fail by stripping at the first thread, because the local condition there is substantially more severe than the average condition that the uniform estimate represents.

4.3 Combined tension and torsion at the thread root

The re-tensioning operation applies tension and torsion simultaneously. The torsion is generated by the friction on the thread flanks and on the bearing surfaces of the coupler, and it is transmitted through the thread to the shank of the rod. The torque required to develop a given tensile force F is

T=Fd22tan⁡(φ+ρ)+Tbearing,

in which φ is the helix angle of the thread,

φ=arctan⁡(Pπd2)=arctan⁡(3π⋅22.051)=arctan⁡(0.0433)=2.48°,

ρ is the friction angle on the thread flank,

ρ=arctan⁡(μcos⁡α)=arctan⁡(0.150.866)=arctan⁡(0.1732)=9.83°,

and Tbearing is the contribution of the friction at the bearing surface of the coupler.

For the nominal friction coefficient μ=0.15, the thread contribution is

tan⁡(φ+ρ)=tan⁡(12.31°)=0.2182,

so that

Tthread=F⋅22.0512⋅0.2182=2.406F.

Including the bearing contribution, the total torque coefficient is approximately 2.42 mm, and the total torque at F=190 kN is

T≈2.42⋅190000=459800 N⋅mm≈460 N⋅m.

The torque coefficient adopted here represents the thread-friction contribution. The bearing contribution is neglected, which corresponds to a well-lubricated thread with a limited bearing surface, as may be found in a turnbuckle with a fitted end connection. Where the bearing surface is larger, as in a standard nut and washer, the bearing friction adds a comparable term, and the total torque coefficient is approximately twice as large; the combined stress at the thread root is then correspondingly higher, and the conclusions of the present section are conservative with respect to the actual condition.

The torque coefficient is strongly dependent on the friction condition. For a lubricated thread with μ=0.10, the friction angle is ρ=6.59∘, the term tan(φ+ρ) is 0.1596, and the torque coefficient is approximately 1.76 mm, giving T≈334 N⋅m at 190 kN. For an unlubricated thread with μ=0.25, the friction angle is ρ=16.10∘, the term tan(φ+ρ) is 0.3362, and the torque coefficient is approximately 3.71 mm, giving T≈704 N⋅m. The torque required to develop the same tension therefore varies by a factor of more than two between the lubricated and unlubricated conditions, and the torsion transmitted to the rod varies correspondingly.

The normal stress at the thread root, evaluated over the minor area A3=324.3 mm2, is

σ=FA3=190000324.3=585.9 MPa.

The shear stress at the thread root, generated by the torque T=460 N⋅m acting on the circular section of diameter d3=20.319 mm, is

τ=16Tπd33=16⋅460000π⋅20.3193=736000026357=279.2 MPa.

The von Mises equivalent stress at the thread root is therefore

σvm=σ2+3τ2=585.92+3⋅279.22=343279+233859=577138=760.0 MPa.

The equivalent stress lies between the yield strength fyb=640 MPa and the ultimate strength fub=800 MPa of the class 8.8 material. The thread root therefore yields during the re-tensioning operation, although the shank verification predicted a utilisation of only 74 % at service load. The difference between the two results is not an arithmetic error: it is the consequence of evaluating two different stress states at two different sections. The shank verification evaluates a uniaxial stress NE d/As at the tensile stress area, whereas the re-tensioning check evaluates a biaxial stress at the thread root under the combined action of tension and torsion. The two checks answer different questions, and the second is not represented by the first.

The combination of tension and torsion also reduces the ductility available at the thread root. Under uniaxial tension, the class 8.8 material exhibits a substantial elongation before fracture, and this ductility is the basis of the plastic redistribution assumptions discussed in Section 6. Under combined tension and torsion, the stress state is biaxial, the equivalent plastic strain at fracture is reduced, and the capacity for redistribution is correspondingly lower. The thread root is therefore not only more highly stressed than the shank, but also less able to accommodate the stress by plastic deformation.

4.4 The strength hierarchy between rod and coupler

The design of threaded fasteners is governed by a principle that is not always stated explicitly but that is fundamental to the reliability of the connection: the failure of the assembly should occur in the bolt rather than in the nut. This principle is implemented in ISO 898-2 by the requirement that nuts be over-tapped and of a property class that ensures the bolt fails before the thread strips. The rationale is that bolt fracture is a ductile failure mode with substantial deformation and visible warning, whereas thread stripping is a shear failure that may occur with little deformation and little warning. The strength hierarchy is therefore a deliberate design feature, not an incidental property of the components.

For the present connection, the hierarchy is inverted. The stripping resistance of the coupler is Fstrip=191.4 kN, whereas the tensile resistance of the rod is Ft, R d=203.3 kN. The ratio is

FstripFt,Rd=191.4203.3=0.942,

so that the thread is approximately 6 % weaker than the rod. The assembly therefore fails by stripping of the coupler thread rather than by rupture of the rod, and the failure mode is the less ductile of the two.

The inversion arises from the combination of two factors. First, the engagement length of 18 mm is below the value required to develop the full strength of the rod, as shown in Section 4.1. Second, the coupler material, S355 with Rm=470 MPa, has a shear strength of 282 MPa, which is substantially lower than the effective tensile strength of the rod material, k2fub=0.9⋅800=720 MPa, divided by the relevant partial factor. Even with a longer engagement, the lower strength of the coupler material would limit the stripping resistance, because the shear area required to develop the rod force would be larger for a weaker material.

The inversion is common in turnbuckles and couplers, where the body is selected for strength and geometry rather than for the strength hierarchy of the threaded assembly. A coupler that is adequate in tension, in the sense that its gross section can carry the rod force, may nevertheless be inadequate in thread shear, because the thread shear area is smaller than the gross section and the shear strength is lower than the tensile strength. The strength hierarchy is therefore not automatically satisfied by a coupler that "looks strong enough", and it must be verified explicitly.

The consequence for the present connection is that the thread is the governing component at the re-tensioning force. The stripping resistance of 191.4 kN is exceeded by the re-tensioning force of 190 kN at the upper end of the range, and the local condition at the first thread is severe even at the lower end. The rod, which the civil engineer verified with a margin of 26 %, is not the component that governs the failure of the assembly. The component that governs is the thread, which the civil engineer did not verify, and which the design brief did not require to be verified.

5. The Re-Tensioning Load Case

5.1 Why re-tensioning is required

A tension member that has been installed and tensioned to its design value does not, in general, retain that tension indefinitely. The tension is reduced over time by a number of mechanisms, each of which is well understood individually but which are seldom considered together in the design of the member.

Creep and relaxation. Under sustained load, the steel of the rod and of the coupler undergoes time-dependent deformation. The relaxation of the tension is small for ordinary structural steel at ambient temperature, but it is not zero, and it is larger for the threaded connection than for the plain shank because the engaged threads are subjected to high local contact pressures that accelerate the time-dependent deformation of the thread flanks.

Settlement. The interfaces between the coupler, the nuts, and the connected components are not perfectly flat, and the surface irregularities are flattened under the contact pressure during the first loading. The resulting settlement reduces the elongation of the member and therefore its tension. The effect is largest immediately after installation and diminishes with time, but it is not eliminated.

Thermal movement. A tension member that spans between two supports at different temperatures, or that is exposed to seasonal temperature variations, undergoes thermal expansion and contraction. If the ends of the member are restrained, the thermal movement is converted into a change of tension. The change may be an increase or a decrease, depending on the sign of the temperature change, but in either case the tension at the time of re-tensioning differs from the design value.

Loss of preload. Where the member is tensioned by tightening a nut against a bearing surface, the preload is reduced by the embedment of the nut into the bearing surface and by the elastic interaction between the nut and the thread. The loss is of the order of a few per cent of the initial preload, but it accumulates over time and over repeated loading cycles.

The re-tensioning operation is performed to restore the tension to its design value, or to a value judged adequate by the operator. It is performed through the thread, by rotating a nut or a turnbuckle body relative to the rod, and it is the force transmitted through the thread during this operation that is the subject of the present section.

5.2 Mechanics of the re-tensioning operation

The re-tensioning operation is not a simple application of a known force. The torque applied to the coupler must overcome three resistances in series.

First, it must overcome the existing tension in the member. The member is already stretched, and the thread is already loaded by the force that corresponds to the existing tension. To increase the tension, the applied torque must first overcome the friction that holds the thread in its current position under that load. The force required to initiate rotation is therefore at least equal to the existing tension, and in practice it is larger, because the static friction at the thread flanks must be overcome before any relative motion occurs.

Second, it must provide the increment of tension that is desired. If the existing tension is N0 and the target tension is N1, the increment is N1−N0. This increment is transmitted through the thread in addition to the existing tension, so that the force in the thread during the operation is at least N1.

Third, it must overcome the friction in the thread and in the bearing surfaces. The friction is not a separate force in the axial direction; it is a resistance to the rotation, and it is expressed as an additional torque. The total torque required to develop a tensile force F in the thread is, from Section 4.3,

T=Fd22tan⁡(φ+ρ)+Tbearing,

in which the first term represents the torque required to advance the thread against the axial load, and the second term represents the friction at the bearing surface of the coupler. Both terms are proportional to F, so that the total torque coefficient K=T/F is independent of the force and depends only on the geometry and on the friction condition.

For the nominal friction coefficient μ=0.15, the torque coefficient is K≈2.42 mm, and the torque required to develop a force of 190 kN is T≈460 N⋅m. For a lubricated thread with μ=0.10, K≈1.76 mm and T≈334 N⋅m. For an unlubricated thread with μ=0.25, K≈3.71 mm and T≈704 N⋅m. The torque required to develop the same force therefore varies by a factor of more than two between the lubricated and unlubricated conditions, and the operator has no means of knowing which condition prevails at the thread flanks at the moment of tightening.

The force transmitted through the thread during the operation is therefore not the service force NE d=150 kN. It is the force required to overcome the existing tension and to provide the increment, and it is at least equal to the target tension N1, which is itself at least equal to the service tension. In the present example, the re-tensioning force is taken to be in the range 185 to 200 kN, corresponding to an existing tension close to the service value and to an increment of the order of 20 % to 30 %.

5.3 The absence of force control

The re-tensioning operation is, in the great majority of practical cases, not force-controlled. The operator applies a torque, not a force, and the relationship between torque and force is subject to a scatter that is difficult to bound without a calibrated wrench and a controlled friction condition.

The scatter arises from three sources. The first is the friction coefficient, which varies with the surface condition, the lubrication, the temperature, and the degree of contamination of the thread. As shown in Section 5.2, the torque coefficient varies by a factor of more than two between the lubricated and unlubricated conditions. The second is the geometry of the thread, which is subject to manufacturing tolerances and to wear. A worn thread has a different helix angle and a different contact condition from a new thread, and the torque coefficient is correspondingly different. The third is the bearing condition at the coupler, which depends on the surface finish, the flatness, and the presence of burrs or contamination.

The combined effect of these sources is a torque–tension scatter of the order of ±25 % to ±30 % for ordinary tightening without a calibrated wrench. The scatter is not a random error that averages out over many operations; it is a systematic uncertainty that applies to each individual operation, and it is the reason why the force transmitted through the thread during re-tensioning cannot be determined from the applied torque with an accuracy better than approximately ±30 %.

The consequence for the present connection is illustrated by the following calculation. Suppose that the operator applies the torque that, under nominal conditions, would produce a force of 190 kN, namely T≈460 N⋅m. Because of the scatter, the actual force produced by this torque may lie anywhere in the range

Nret=TK(1±0.30)=190⋅(1±0.30)=133to247 kN.

The upper bound of this range, 247 kN, exceeds the stripping resistance of the coupler thread, Fstrip=191.4 kN, by approximately 29 %, and it exceeds the tensile resistance of the rod, Ft, R d=203.3 kN, by approximately 21 %. The lower bound, 133 kN, is below the service load and would leave the member under-tensioned. The operator has no means of distinguishing between these outcomes, because the only quantity that is measured is the torque, and the torque does not determine the force.

In practice, the situation is worse than this calculation suggests, because the operator frequently does not measure the torque at all. The re-tensioning is performed with a wrench of convenient length, and the operator applies a force judged by feel until the connection "seems tight". The force applied in this way is not controlled, not recorded, and not reproducible, and it may lie anywhere within a range that is considerably wider than the ±30 % associated with a torque wrench. The re-tensioning force is therefore not merely uncertain; it is, in the ordinary case, unknown.

5.4 Consequence: the force exceeds the thread capacity

The consequence of the preceding analysis is that the force transmitted through the thread during re-tensioning is not the service force for which the member was verified. It is a larger force, applied without force control, and it may exceed the capacity of the thread even when the service force is well below the capacity of the rod.

For the present connection, the comparison is as follows. The service force is NE d=150 kN, which is 74 % of the rod tensile resistance Ft, R d=203.3 kN and 78 % of the thread stripping resistance Fstrip=191.4 kN. At service load, therefore, both the rod and the thread have a margin, and the member "resists" in the sense of the civil engineer's verification.

The re-tensioning force is in the range 185 to 200 kN under nominal conditions, and it may reach 247 kN at the upper bound of the torque–tension scatter. The nominal range already approaches the thread stripping resistance: at 190 kN, the force is 99 % of Fstrip, and at 200 kN it exceeds Fstrip by approximately 4 %. The upper bound of the scatter range exceeds Fstrip by 29 % and Ft, R d by 21 %.

The thread is therefore the component that governs the failure of the assembly during re-tensioning. The failure occurs by stripping of the coupler thread, at a force that lies between the nominal re-tensioning force and the upper bound of the scatter range, and it occurs before the rod reaches its tensile resistance. The failure mode is the shear failure of the thread, which is the less ductile of the two failure modes, and it occurs with little warning.

The result is not a consequence of an error in the civil engineer's verification. The rod is adequate for the service load, and the verification correctly establishes this. The result is a consequence of the fact that the re-tensioning force is larger than the service force, that it is applied without force control, and that the thread capacity is lower than the rod capacity. None of these three factors is represented in the civil engineer's verification, and none of them is ordinarily included in the design brief.

5.5 Why the load case is absent from the design brief

The re-tensioning load case is absent from the design brief for a reason that is structural rather than accidental. The design brief is ordinarily formulated in terms of the permanent and variable actions that the structure must resist during its service life, and the re-tensioning operation is classified as a construction or erection phase action rather than as a permanent design action. It is transient, it is performed by the contractor rather than by the structure, and it is not part of the load combinations that the design rules require to be verified.

The consequence of this classification is that the re-tensioning force is not included in the design calculations for the tension member. The civil engineer's model treats the rod as a bar in tension with a single design force NE d, and the verification is performed against this force. The re-tensioning force is not represented in the model, and the thread capacity is not verified against it. The verification is complete within its scope, but the scope does not include the load case that governs the failure.

The classification is not unreasonable in itself. The re-tensioning operation is indeed transient, and it is indeed performed by the contractor. But the classification has a consequence that is not always recognised: the component that governs the failure of the assembly during the transient operation is not the component that governs the resistance during the permanent condition. The rod governs the permanent condition, and the thread governs the transient condition. The verification addresses the permanent condition, and the failure occurs in the transient condition.

The remedy is not to reclassify the re-tensioning operation as a permanent action, which would be artificial, but to include it explicitly in the design brief as a separate load case with its own verification. The verification of the thread against the re-tensioning force is a distinct check, performed with a distinct method, and it is not substituted by the verification of the rod against the service force. The two checks address two different conditions, and the integrity of the assembly requires both.

A further consequence of the repeated nature of the re-tensioning operation must be noted. Each re-tensioning cycle produces relative displacement between the rod thread and the coupler thread under high contact pressure, as discussed in Section 1. The displacement produces wear of the thread flanks, which reduces the effective engagement length and increases the friction coefficient. The capacity of the thread therefore decreases with each cycle, while the force required to re-tension the member may increase as a result of the increased friction. The two effects act in the same direction: the margin of the thread against stripping is reduced by each re-tensioning operation, and the reduction is cumulative over the service life of the member. A thread that is marginally adequate at the first re-tensioning may be inadequate at the fifth, and the design brief that does not include the re-tensioning load case does not detect either condition.

6. Plastic Distribution and Failure Mode

6.1 Ductile rupture of the rod versus shear failure of the thread

The two failure modes identified in Sections 3 and 4 are not equivalent, either in their mechanics or in the warning they provide.

Rupture of the rod is a tensile failure of a ductile material. The class 8.8 steel exhibits a well-defined yield plateau, a substantial uniform elongation, and a reduction of area at fracture; the minimum elongation at fracture specified in ISO 898-1 for property class 8.8 is A=12 %. Before fracture, the rod undergoes visible elongation, the tensioned member visibly lengthens, and the loss of tension is progressive. The failure is preceded by necking at the threaded section, and the deformation is distributed over a length of the order of the diameter. The failure is therefore ductile in the conventional sense: it is preceded by large plastic deformation, it is visible, and it occurs at a load that is well defined by the tensile resistance Ft, R d.

Stripping of the thread is a shear failure of the engaged threads. The failure occurs on the cylindrical shear surface that separates the material of the coupler thread from the body of the coupler, and it progresses thread by thread as the shear capacity of each successive thread is exhausted. The deformation associated with the failure is small: the relative axial displacement between rod and coupler at the onset of stripping is of the order of the elastic deformation of the engaged threads, which is a fraction of a millimetre. There is no elongation of the member, no visible lengthening, and no progressive loss of tension before the failure. The failure occurs suddenly, in the sense that the transition from a loaded but intact connection to a stripped connection is not preceded by a deformation that can be observed.

The asymmetry between the two failure modes is the physical basis of the strength hierarchy principle discussed in Section 4.4. The design of threaded fasteners deliberately arranges for the bolt to fail before the nut, precisely because the bolt failure is ductile and visible while the nut failure is not. In the present connection, the hierarchy is inverted, and the assembly therefore fails by the less ductile of the two modes.

6.2 The limited plastic redistribution over the engaged threads

The nominal stripping resistance Fstrip=191.4 kN calculated in Section 4.1 represents the load at which all engaged threads reach their shear capacity simultaneously. This value is an upper bound, and it is attained only if the load is fully redistributed from the first thread, which yields first, to the subsequent threads, which retain reserve capacity.

The capacity for such redistribution is limited, for three reasons.

First, the elastic load distribution over the engaged threads is strongly non-uniform. As shown in Section 4.2, the first thread carries approximately 33 % of the total load, and its local shear stress at Nret=190 kN is 554 MPa, approximately 1.96 times the shear strength of 282 MPa. The first thread therefore yields at a load well below the nominal stripping resistance, and the subsequent threads must accept the load that the first thread can no longer carry.

Second, the redistribution is limited by the geometry of the thread. When the first thread yields in shear, the material that has yielded is confined between the rod thread and the coupler thread, and it cannot deform freely. The stress state in the yielded zone is one of high hydrostatic compression, which suppresses the plastic flow that would be required for a full redistribution. The yielded thread does not shed its load completely; it continues to carry a substantial fraction of its elastic share, and the load is transferred to the subsequent threads only partially.

Third, the redistribution is limited by the number of threads available. With an engagement length of Le=18 mm, corresponding to approximately six engaged threads, the reserve capacity available in the threads beyond the first is small. If the first thread carries 33 % of the load elastically and yields, the remaining five threads must carry the balance, and the increase in their share is correspondingly large. The redistribution therefore requires the subsequent threads to be loaded close to their capacity, which they are not, because the elastic distribution assigns them progressively smaller shares. The result is that the stripping progresses sequentially, thread by thread, at a load that lies between the load at which the first thread yields and the nominal stripping resistance.

The practical consequence is that the actual stripping resistance of the connection lies below the nominal value Fstrip=191.4 kN, and the margin between the re-tensioning force and the stripping resistance is correspondingly smaller than the nominal calculation indicates. The reduction is difficult to quantify without a detailed elastic–plastic contact analysis, but its direction is unambiguous: the limited redistribution capacity of the thread makes the stripping resistance lower than the uniform-stress estimate, not higher.

6.3 Multiaxial stress state and reduced ductility at the thread root

The thread root is subjected to a multiaxial stress state even under pure axial loading, and the multiaxiality is intensified during re-tensioning by the superposition of torsion.

Under pure axial load, the stress state at the thread root is triaxial, with a hydrostatic tensile component generated by the notch geometry. The notch at the thread root constrains the lateral contraction of the material, and the resulting hydrostatic tension reduces the equivalent plastic strain at fracture. The reduction is a well-established feature of notched tensile specimens, and it is the reason why the elongation at fracture measured on a smooth specimen is not representative of the deformation capacity of the thread root.

Under combined tension and torsion, as in the re-tensioning operation, the equivalent stress at the thread root reaches σvm=760.0 MPa, as calculated in Section 4.3, which lies between the yield strength fyb=640 MPa and the ultimate strength fub=800 MPa. The thread root therefore yields during re-tensioning, and the yielding occurs under a stress state that combines the hydrostatic tension of the notch with the shear of the torsion. The capacity for plastic deformation under this combined state is lower than under uniaxial tension, and the deformation that precedes fracture is correspondingly smaller.

The consequence for the failure mode is significant. The plastic redistribution that would be required to mobilise the full stripping resistance of the thread depends on the capacity of the thread root to deform without fracture. Under combined tension and torsion, this capacity is reduced, so that the redistribution is more limited than the uniaxial analysis would suggest. The thread root is therefore not only more highly stressed than the shank, as shown in Section 4.3, but also less able to accommodate that stress by plastic deformation. The two effects act in the same direction: they reduce the force at which the thread fails, and they increase the abruptness of the failure.

6.4 Stress concentration at the thread root

The thread root is a geometric discontinuity with a small root radius. For a metric thread of pitch P=3 mm, the root radius is of the order of r≈0.13P≈0.39 mm, and the stress concentration factor for axial loading is of the order of Kt≈3 to 5, depending on the exact profile and on the method of evaluation.

Under static loading, the stress concentration at the thread root is partly relieved by local yielding, and its effect on the static resistance is incorporated in the calibration factor k2=0.9 of the tensile verification. Under cyclic loading, however, the stress concentration is not relieved, and it governs the fatigue behaviour of the connection. The thread root is the location at which fatigue cracks initiate in threaded members subjected to fluctuating tension, and the fatigue strength of a threaded connection is substantially lower than that of the plain shank for this reason.

In the present context, the stress concentration has two consequences. First, it contributes to the triaxiality of the stress state at the thread root, and therefore to the reduction of ductility discussed in Section 6.3. Second, it makes the thread root the location at which any pre-existing defect, such as a machining mark, a corrosion pit, or a wear scar, produces a local stress that is substantially higher than the nominal stress. A thread that has been worn by repeated tensioning, as discussed in Section 1 and in Section 5.5, has a modified root geometry and a rougher surface, and the local stress concentration is correspondingly higher. The wear therefore degrades the thread not only by reducing the shear area but also by increasing the local stress at the root.

6.5 The thread as the governing component: a mechanism, not a section

The analysis of Sections 4 to 6 supports a conclusion that is, in a sense, the central conclusion of the article. The thread is the governing component of the connection, but it is not the governing component in the sense in which a structural engineer ordinarily understands the term. It does not have the smallest cross-sectional area: the shear area of the engaged thread, Ashear=678.6 mm2, is approximately twice the minor area of the thread root, A3=324.3 mm2, and approximately twice the tensile stress area, As=353 mm2. It is not the component with the lowest nominal strength: the coupler material, S355, has a yield strength of 355 MPa, which is lower than the 640 MPa of the class 8.8 rod, but this difference is not in itself sufficient to make the thread governing.

The thread is the governing component because its resistance is governed by a mechanism that the section verification does not represent. That mechanism comprises the shear of the engaged threads, the non-uniform distribution of load over them, the limited capacity for plastic redistribution, the multiaxial stress state at the thread root under combined tension and torsion, and the degradation of the thread by wear. Each of these is a distinct physical process, and none of them is captured by the tensile resistance Ft, R d, which represents rupture of a threaded section under uniaxial tension.

The distinction has a general form that extends beyond the present example. In a structural connection, the resistance of the assembly is the resistance of its weakest component, and the weakest component is not necessarily the one with the smallest cross-section. It is the one whose resistance is governed by the most severe mechanism, and the severity of the mechanism depends on the stress state, on the load distribution, on the material behaviour, and on the degradation processes to which the component is subjected. A verification that addresses only the cross-section, and only the uniaxial stress state, therefore addresses only one of the possible mechanisms, and it may fail to identify the component that actually governs.

This is the sense in which the civil engineer's verification and the mechanical engineer's verification answer different questions. The civil engineer asks whether the rod will rupture under the service load, and the answer is yes or no, and it is correct. The mechanical engineer asks whether the thread will transmit the force that is actually applied to it, and the answer depends on the engagement length, on the friction condition, on the re-tensioning force, and on the wear of the thread. The two questions are not equivalent, and the answer to the first does not determine the answer to the second.

The failure mode of the present connection follows from this distinction. The rod satisfies the civil engineer's verification with a margin of 26 % at service load, and it does not rupture. The thread fails during re-tensioning, at a force that lies between the nominal re-tensioning force and the upper bound of the torque–tension scatter, and it fails by a mechanism that the civil engineer's verification does not represent. The failure is therefore not a consequence of an inadequate rod but of an unverified thread, and the verification that would have detected it is the one that the design brief did not require.

7. Conclusion

7.1 Summary of findings

The present article has examined the failure of a threaded tension member under a load case that is ordinarily absent from the design brief: the re-tensioning of an element that has lost part of its initial tension. The analysis was developed for a representative configuration consisting of an M24 threaded rod of property class 8.8, engaged in a coupler of S355 steel over an engaged length of 18 mm, and loaded in service to 150 kN.

The civil engineer's verification of the rod was carried out and found to be satisfied. The design tensile resistance of the threaded section is Ft, R d=203.3 kN, and the utilisation at service load is 74 %. The stress in the tensile stress area at service load is 425 MPa, well below the yield strength of the class 8.8 material. On the basis of this verification, the member resists with a margin of approximately 26 %.

The mechanical engineer's verification of the thread was then carried out and found to give a different conclusion. The stripping resistance of the coupler thread, estimated from the shear area of the engaged thread and the shear strength of the coupler material, is Fstrip=191.4 kN. The stripping resistance is therefore lower than the tensile resistance of the rod by approximately 6 %, and the strength hierarchy between rod and coupler is inverted. The engagement length required to develop the full strength of the rod is 19.13 mm, corresponding to Le/d=0.80; the actual engagement of 18 mm, corresponding to Le/d=0.75, lies just below this value.

The re-tensioning load case was analysed and shown to produce a force that exceeds the stripping resistance of the thread even under nominal conditions. The re-tensioning force lies in the range 185 to 200 kN when the operation is performed with a torque wrench under controlled conditions, and the upper bound of the range exceeds Fstrip by approximately 4 %. When the torque–tension scatter of ±30 % is admitted, the force transmitted through the thread may reach 247 kN, which exceeds Fstrip by 29 % and Ft, R d by 21 %. In the ordinary case, in which the operation is performed by feel without a torque wrench, the applied force is not merely uncertain but unknown.

The stress state at the thread root during re-tensioning was examined and shown to produce yielding under combined tension and torsion. At 190 kN, the nominal tensile stress at the thread root is 585.9 MPa, the shear stress produced by the torque is 279.2 MPa, and the von Mises equivalent stress is 760.0 MPa, which lies between the yield strength and the ultimate strength of the class 8.8 material. The torque required to produce this force varies by a factor of more than two between the lubricated and unlubricated conditions, so that the friction condition at the thread governs the stress state to which the rod is subjected during the operation.

The analysis of the failure modes showed that the two modes are not equivalent. Rupture of the rod is a ductile tensile failure, preceded by visible elongation and progressive loss of tension. Stripping of the thread is a shear failure of the engaged threads, with little deformation and little warning, and its resistance is limited by the non-uniform distribution of load over the engaged threads, by the reduced capacity for plastic redistribution, and by the degradation of the thread under repeated tensioning. The thread is therefore the governing component of the assembly, not because it has the smallest cross-section, but because its resistance is governed by a mechanism that the section verification does not represent.

7.2 Engineering takeaways

Five conclusions of direct engineering relevance follow from the analysis.

The verification of the shank is not the verification of the threaded assembly. The tensile resistance Ft, R d addresses rupture of the threaded section under a uniaxial tensile force. It does not address thread stripping, the distribution of load over the engaged threads, combined tension and torsion at the thread root, the strength hierarchy between rod and coupler, or the degradation of the thread under repeated tensioning. Each of these is a distinct failure mode or degradation mechanism, governed by a distinct resistance, and none of them is represented by the tensile resistance formula. A member that satisfies the tensile verification is verified against rupture, and against rupture only.

The re-tensioning force is not the service force. The force transmitted through the thread during re-tensioning is larger than the service force, because it must overcome the existing tension and provide the increment required to restore the design tension, and it is applied without force control. For the present connection, the re-tensioning force exceeds the thread stripping resistance even under nominal conditions, while the service force is well below both the stripping resistance and the tensile resistance. The load case that governs the failure is therefore not the load case for which the member was designed.

The torque–tension relationship is not a reliable means of controlling the force. The torque required to develop a given tension varies by a factor of more than two between the lubricated and unlubricated conditions, and the resulting scatter in the force is of the order of ±30 % for tightening without a calibrated wrench. The force transmitted through the thread during re-tensioning therefore cannot be determined from the applied torque with an accuracy better than approximately ±30 %, and in the ordinary case, in which the torque is not measured, the force is not known at all. A design that relies on the operator to "tighten until it feels right" does not control the force to which the thread is subjected.

The strength hierarchy between rod and coupler is a design requirement, not an incidental property. The principle that the assembly should fail in the rod rather than in the thread is implemented in ISO 898-2 by the requirement that nuts be over-tapped and of a suitable property class. The principle applies equally to couplers and turnbuckles, and it must be verified explicitly. A coupler that is adequate in tension, in the sense that its gross section can carry the rod force, may nevertheless be inadequate in thread shear, because the shear area is smaller than the gross section and the shear strength is lower than the tensile strength. For the present connection, the ratio Fstrip/Ft, R d=0.942 shows that the hierarchy is inverted, and the inversion is the direct cause of the failure mode.

The thread is the governing component by mechanism, not by section. The resistance of the assembly is the resistance of its weakest component, and the weakest component is not necessarily the one with the smallest cross-section. It is the one whose resistance is governed by the most severe mechanism, and the severity of the mechanism depends on the stress state, on the load distribution, on the material behaviour, and on the degradation processes to which the component is subjected. A verification that addresses only the cross-section, and only the uniaxial stress state, may therefore fail to identify the component that actually governs.

7.3 Recommendations for design

On the basis of the preceding analysis, the following procedure is recommended for the design of threaded tension members in which the member may be re-tensioned during its service life.

The tensile verification of the rod should continue to be performed, as it is at present, in accordance with the rules for tension members. It establishes that the rod will not rupture under the service load, and it is correct within its scope.

The thread should be verified explicitly, with the methods of the discipline concerned with threaded fasteners. The verification should include the stripping resistance of the engaged thread, evaluated with the shear area of the engagement and the shear strength of the engaging material; the distribution of load over the engaged threads; the combined tension and torsion at the thread root under the tightening and re-tensioning torques; and the strength hierarchy between the rod and the engaging component. The engagement length should be selected so that the stripping resistance exceeds the tensile resistance of the rod, with a margin that accounts for the scatter in the material properties and in the engagement geometry.

The re-tensioning load case should be included explicitly in the design brief, with its own design force and its own verification. The force should be determined from the existing tension, the required increment, and the friction in the thread and in the bearing surfaces, and it should be bounded at its upper value by the scatter of the torque–tension relationship. The thread should be verified against this force, in addition to the verification against the service force.

The lubrication condition of the thread should be specified in the design, and it should be maintained during the service life of the member. The coefficient of friction enters both the torque required to tension the member and the torsion transmitted to the rod, and an unlubricated thread produces both a higher torque and a higher stress at the thread root for the same tensile force. The specification of a lubrication condition is therefore not a matter of convenience but a design requirement that affects the stress state to which the member is subjected during re-tensioning.

Where the member is required to be re-tensioned repeatedly, the effect of wear on the thread should be considered. The relative displacement between the rod thread and the coupler thread under high contact pressure produces wear of the thread flanks, and the wear reduces the effective engagement length and increases the friction coefficient. Both effects reduce the margin of the thread against stripping, and the reduction is cumulative over the service life of the member.

7.4 Concluding remarks

The analysis presented in this article has shown that a threaded tension member can satisfy the verification that is ordinarily performed and nevertheless fail by a mechanism that the verification does not represent. The failure is not a consequence of an arithmetic error in the verification, nor of an inadequate choice of diameter, nor of a defective material. It is a consequence of a difference in scope between the verification that is performed and the verifications that the integrity of the assembly requires.

The verification that is performed, and that is required by the design rules for tension members, addresses rupture of the threaded section under the service load. The verifications that are required for the integrity of the assembly address the thread stripping, the load distribution over the engaged threads, the combined tension and torsion at the thread root, and the strength hierarchy between the rod and the coupler. These verifications belong to the discipline of threaded fasteners, and they are performed as a matter of course in mechanical assemblies. They are not performed for tension members in civil structures, because the load case that would require them — the re-tensioning of the stretched element — is classified as a construction phase action and is not included in the design brief.

The general principle that emerges from the analysis is that a tension member is a system of components, and the resistance of the system is the resistance of its weakest component. The weakest component is not necessarily the one with the smallest cross-section; it is the one whose resistance is governed by the most severe mechanism. In the present connection, the weakest component is the thread, and the mechanism that governs it is the shear of the engaged threads under a force that is larger than the service force and is applied without force control. The verification that would identify this mechanism is the mechanical engineer's verification of the thread, and it is the verification that the design brief does not require.

The principal engineering conclusion is therefore that the civil engineer's verification of the shank and the mechanical engineer's verification of the thread are not alternatives, and neither substitutes for the other. The first establishes that the rod will not rupture under the service load; the second establishes that the thread will transmit the force that is actually applied to it. Both are necessary for the integrity of the assembly, and the omission of either leaves the assembly verified against one failure mode and unverified against the other. The failure of the present connection is the consequence of this omission, and the remedy is not to strengthen the rod but to complete the verification.